Table 2-2. trip led truth table -9 – Basler Electric BE1-700 User Manual

Page 37

Advertising
background image

Table 2-2. Trip LED Truth Table

Trip

Pickup

Targets

Trip LED

No

No

No

Off

No

No

Yes

On

No

Yes

No

Flash

No

Yes

Yes

Flash

Yes

No

No

On

Yes

No

Yes

On

Yes

Yes

No

On

Yes

Yes

Yes

On

11.) Is the IRIG signal modulated or demodulated?

The BE1-700 accepts an IRIG-B signal that is demodulated (dc level-shifted digital signal). See
Section 1, General Information, Operational Specifications, for additional information.

12.) Can the IRIG signal be daisy-chained to multiple BE1-700 units?

Yes, multiple BE1-700 units can use the same IRIG-B input signal by daisy chaining the BE1-700
inputs. The burden data is nonlinear, approximately 4 kilo-ohms at 3.5 Vdc and 3 kilo-ohms at 20
Vdc. See Section 1, General Information, Operational Specifications, and Section 3, Input and
Output Functions
, for additional information.

13.) How are reports and other information obtained from the relay saved in files for future use?

BESTCOMS can be used to capture records information. See Section 6, Reporting and Alarm
Functions, Fault Reporting, Fault Summary Reports
.

Also, any information reported by the relay can be transferred to a text file and saved for future use.
Text received from the relay to your terminal emulation software can be selected and copied to the
clipboard. The clipboard contents are pasted into any word processor such as Microsoft

® Notepad

and then saved with an appropriate file name.

You may also use your terminal emulation software to store reports in files as they are received
from the relay. In BESTVIEW, this is accomplished by using the "log/open log file" function. In
Microsoft HyperTerminal, this function is available through the "capture text" feature. Microsoft
Windows Terminal provides this function through the "received text file" feature.

14.) How can I check the version number of my BE1-700?

The application version can be found in three different ways: One, use HMI, Screen 4.7. Two, use
the RG-VER command with the ASCII command interface. Three, use BESTCOMS for BE1-700.
(The version is provided on the General Information tab of the General Operation screen.)

9376700990 Rev M