Backup/restore, Backup/restore -9 – Basler Electric BE1-700 User Manual

Page 401

Advertising
background image

Setting

Value

Function

Alert Logic

SG-EMAIL1,
SG-EMAIL2 . . .
SG-EMAIL7

This setting selects which BESTnet logic equation will cause
e-mail message(s) to be sent by the BE1-700 relay. The
BESTnet logic equations are defined in BESTCOMS.

Trigger Interval

0 to 99,999 seconds

Minimum time to detect a true ALERT LOGIC condition. A
setting other than zero causes the BE1-700 to wait the
specified time before sending another e-mail message for
additional occurrences of the same trigger.

Enable Reminder
Notifications

Unchecked

Send only one alert e-mail per trigger.

Checked

Send e-mails periodically for as long as the ALERT LOGIC
remains true.

Reminder Interval

0 to 99,999 seconds

Repetition interval for reminder e-mails, if enabled. A value of
zero is NOT recommended and will send many e-mails per
second while the ALERT LOGIC is true.

Backup/Restore

Purpose: Allows BESTnet configuration to be saved in a file on the PC or loaded from a file. This is useful
for saving a configuration before making a change, or for copying a configuration from one BE1-700 to
another.

Backup/Restore Configuration screen settings are shown in Figure 15-7 and described in Table 15-5.

Figure 15-7. Backup/Restore Configuration Screen

NOTE

The BESTnet configuration backup file will contain only settings saved by the
BESTnet configuration applet. To save all settings from a BE1-700, save the
BESTnet settings with this function, then use BESTCOMS to save the protection
settings to a .BST file. These two files together will contain all configuration
information for a BE1-700 relay.

9376700990 Rev M

BE1-700 BESTnet Communication

15-9

Advertising
This manual is related to the following products: