APPENDIX A

• TIME OVERCURRENT

CHARACTERISTIC CURVES

GENERAL

Basler Electric inverse time overcurrent systems (ANSI Device 51) provide time/current characteristic
curves that very closely emulate most of the common electro-mechanical, induction disk relays that were
manufactured in North America. To further improve proper relay coordination, selection of integrated reset
or instantaneous reset characteristics is also provided.

CURVE SPECIFICATIONS

Timing Accuracy (All 51 Functions):

Within

±5% or ±1½ cycles, whichever is greater,

for time dial settings greater than 0.1 and
multiples of 2 to 40 times the pickup setting but
not over 150 A for 5 A CT units or 30 A for 1 A CT
units.


Sixteen inverse time functions, one fixed time
function, and one programmable time function
can be selected. Characteristic curves for the
inverse and definite time functions are defined by
the following equations and comply with IEEE Std
C37.112 - 1996 - IEEE Standard Inverse-Time
Characteristic Equations for Overcurrent Relays
.

K

D

B

C

M

D

A

T

N

T

+

+

=

Equation A-1

1

M

D

R

T

2

R

=

Equation A-2


T

T

= Time to trip when M

≥ 1

T

R

= Time to reset if relay is set for integrating

reset when M

< 1. Otherwise, reset is 50

milliseconds or less

D

= TIME DIAL setting (0.0 to 9.9)

M

= Multiple of PICKUP setting (0 to 40)

A, B, C, N, K

= Constants for the particular curve

R

= Constant defining the reset time.


Table A-1 lists time characteristic curve
constants. See Figures A-1 through A-17 for
graphs of the characteristics.

9376700990 Rev M

BE1-700 Time Overcurrent Characteristic Curves

A-1