Page 18: Metered frequency values and accuracy (be1-700v), Calculated values and accuracy, Operational specifications -6, Metered current values and accuracy (be1-700c) -6, Metered voltage values and accuracy (be1-700v) -6, Calculated values and accuracy -6, Figure 1-1. style number identification chart -6

Advertising
background image

Figure 1-1. Style Number Identification Chart

OPERATIONAL SPECIFICATIONS

Depending on the style ordered, BE1-700 relays have the following features and capabilities:

Metered Current Values and Accuracy (BE1-700C)

Current Range

5 Aac Nominal:

0.5 to 15 Aac

1 Aac Nominal:

0.1 to 3.0 Aac

Accuracy:

±1% of reading, ±1 least significant digit at 25°C

Temperature Dependence:

≤ ±0.02% per °C

Metered Voltage Values and Accuracy (BE1-700V)

Voltage Range

3-wire:

0 to 300 V

L-L

4-wire:

0 to 300 V

L-L

Accuracy (10 to 75 hertz)

50 V to 300 V:

±0.5% of reading, ±1 least significant digit at 25°C

Temperature Dependence:

≤ ±0.02% per °C

Metered Frequency Values and Accuracy (BE1-700V)

Frequency Range:

10 to 75 Hz

Accuracy:

±0.01 hertz, ±1 least significant digit at 25°C

Sensing Input

3-wire:

Phase A – B

4-wire:

Phase A – Neutral

Minimum Frequency Tracking Voltage:

10 V rms

Calculated Values and Accuracy

Demand

Range:

0.1 to 1.5 nominal

Type:

Exponential

Accuracy:

±1% of reading ±1 digit at 25°C

Temperature Dependence:

≤ ±0.02% per °C

Interval:

1 to 60 min

1-6

BE1-700 General Information

9376700990 Rev M