Settings (S) Command Descriptions

Reading All Settings

All user programmable settings can be listed using the S command. This read-only command is useful for
documenting relay status during installation. The settings retrieved by the S command can be saved to a
standard text file and sent to another relay to be configured with the same settings. This type of settings
transfer takes less than one minute.

S Command
Purpose:

Read all relay setting parameters

Syntax:

S

Example:

S

The S command returns the values of relay setting parameters in the same form that they are
programmed. It can be used at the end of a programming session to make a record of the relay settings.
If saved in a file, the report can be sent to another BE1-700 that will use the same settings. Because the
report that is created is a set of commands, sending the report to a different relay re-programs that relay
with the settings contained in the S report.

Reading Specific Groups of Settings

While the S command is useful for reading all relay settings, several commands are available to read
specific groups of settings.

SA Command
Purpose:

Read all alarm settings for Major and Minor alarms

Syntax:

SA

Example:

SA

SA Command Example:
Example 1.

Read all alarm settings.

>SA

SA-BKR1=0,0;

SA-BKR2=0,0;

SA-BKR3=0,0

SA-DIP=0.00;

SA-DIN=0.00;

SA-DIQ=0.00

SA-LGC=0

SA-MAJ=25

SA-MIN=29

SA-RESET=0

SB Command
Purpose:

Read all breaker settings

Syntax:

SB

Example:

SB

SB Command Example:
Example 1.

Read all breaker settings.

>SB

SB-DUTY=0,0.000e+00

SB-LOGIC=/IN1

SG Command
Purpose:

Read all general settings

Syntax:

SG

Example:

SG


9376700990 Rev M

BE1-700 ASCII Command Interface

11-5