Negative-sequence voltage (47) (be1-700v), Negative-sequence voltage (47) (be1-700v) -35, Table 13-56. 47 pickup test commands -35 – Basler Electric BE1-700 User Manual

Page 331: Table 13-55

Advertising
background image

Table 13-55. 27X and 59X/159X Pickup and Time Delay Settings

Pickup and Time Delay Settings

Purpose

Undervoltage

Overvoltage

S0-27X=50,2S,0

S0-59X/159X=110,2S

Sets 27X PU at 50 V, 59X/159X at 110 V, TD at 2 sec,
UV Inhibit disabled.

S0-27X=,5S

S0-59X/159X=,5S

Sets 27X PU at 50 V, 59X/159X at 110 V, TD at 5 sec.

S0-27X=,10S

S0-59X159X=,10S

Sets 27X PU at 50 V, 59X/159X at 110 V, TD at 10 sec.

Step 2: Prepare to monitor the 27X and 59X/159X timings. Timing accuracy is verified by measuring the

elapsed time between a sensing voltage change and OUT1 closing.

Step 3: Connect and apply a single-phase, 80 Vac, 3

rd

harmonic voltage source to Terminals C17

(polarity) and C18 (non-polarity). Refer to Figure 12-4 for terminal locations.

Step 4: Step the voltage down to 45 volts. Measure the time delay and verify the accuracy of the 27X

time delay setting. Timing accuracy is

±5% or ±3 cycles of the time delay setting.

Step 5: Step the voltage up to 115 volts. Measure the time delay and verify the accuracy of the

59X/159X time delay setting. Timing accuracy is

±5 percent or ±3 cycles of the time delay

setting.

Step 6: Repeat Steps 5 and 6 for the middle and upper time delay settings of Table 13-55.

Step 7: (Optional.) Repeat Steps 2 through 6 for Setting Group 1.

Negative-Sequence Voltage (47) (BE1-700V)

Purpose: To verify the operating accuracy of the 47 protection element.

Reference Commands: SL-47, SL-VO, SL-GROUP, RG-STAT

Negative-Sequence Voltage Pickup Verification

Step 1: Prepare the 47 pickup function for testing by transmitting the commands in Table 13-56 to the

relay. Reset targets.

Table 13-56. 47 Pickup Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE settings.

Y

Confirm overwrite.

SL-N=47

Sets 47 as custom logic name.

SL-27P=0

Disables 27P.

SL-59P=0

Disables 59P.

SL-47=1,0

Enables 47, disables blocking.

SP-60FL=ENA,PN

Removes 60FL block from 47 element.

SL-VO1=47T

Enables OUT1 to close for 47 trip.

SG-TRIG=47T,47PU,0

Enables 47 to log and trigger fault recording.

SG-TARG=47

Enables 47 target.

EXIT;Y

Exit and save settings.

Step 2: Using Table 13-57 as a guide, transmit the first row of setting commands to the relay.

9376700990 Rev M

BE1-700 Testing and Maintenance

13-35

Advertising
This manual is related to the following products: