Basler Electric BE1-700 User Manual

Page 220

Advertising
background image

SL-62=2,VO10,0 (optional target reset)
SL-79=1,VO8,/IN1,VO14,0
SL-081=1,O
SL-181=1,O
SL-281=1,VO14
SL-381=1,VO14
SL-VO1=VO13
SL-VO2=79C
SL-VO3=/VO13
SL-VO6=81T*181T
SL-VO7=281T*381T
SL-VO8=VO6
SL-VO10=/VO6*IN1*IN3*VO7
SL-VO13=VO6+VO14
SL-VO14=/VO10*VO13

Add +81T+181T to BUS SG-TRIG. Replace the ,0 with ,62 at the end of BUS SG-TARG.
The resulting OC-UF-79 setting logic is as follows:

SL-50TP=1,79SCB; SL-50TN=1,79SCB+/IN4; SL-50TQ=1,79SCB+/IN4
SL-150TP=1,0; SL-150TN=1,0; SL-150TQ=1,0
SL-51P=1,0
SL-51N=1,/IN4
SL-51Q=1,/IN4
SL-151N=0,0
SL-27P=0,0
SL-59P=0,0; SL-59X=0,0
SL-47=0,0
SL-62=2,VO10,0
SL-162=0,0,0
SL-79=1,VO8,/IN1,VO12+VO14,150TPT+150TNT+150TQT+/IN2
SL-81=1,0
SL-181=1,0
SL-281=1,/VO14
SL-381=1,/VO14
SL-481=0,0
SL-581=0,0
SL-BF=0,0,0
SL-GROUP=1,0,0,0,0,/0
SL-43=0
SL-143=0
SL-101=0
SL-VOA=0
SL-VO1=VO11+VO13
SL-VO2=79C
SL-VO3=/VO13
SL-VO4=ALMMIN
SL-VO5=ALMMAJ
SL-VO6=81T*181T
SL-VO7=281T*381T
SL-VO8=VO6+VO11
SL-VO9=150TPT+150TNT+150TQT+/IN2
SL-VO10=/VO6*VO7*IN1*IN3
SL-VO11=50TPT+150TPT+50TNT+150TNT+50TQT+150TQT+51PT+51NT+51QT
SL-VO12=50TPPU+150TPPU+50TNPU+150TNPU+50TQPU+150TQPU+51PPU+51NPU+51QPU
SL-VO13=VO6+VO14
SL-VO14=/VO10*VO13
SL-VO15=0

8-38

BE1-700 Application

9376700990 Rev M

Advertising
This manual is related to the following products: