Breaker failure (bf) (be1-700c), Breaker failure (bf) (be1-700c) -41, Table 13-66. bf pickup test commands -41 – Basler Electric BE1-700 User Manual

Page 337

Advertising
background image

Step 6: Decrease the Auxiliary voltage input (VTX) until OUT1 opens. Slowly increase the voltage until

OUT1 closes. Pickup should occur within

±2% of the Delta V setting. Dropout should occur at

97% to 98% of actual pickup.

Step 7: Repeat Step 6 for the Line voltage input (VTP). Return voltage inputs to 120 Vac, 50 or 60

hertz, 0 degrees.

Step 8: Swing the angle between voltage source 1 and 2 until the OUT1 opens. Slowly decrease the

angle until OUT1 closes. Pickup should occur within

±2° of the Delta Angle setting on the

leading and lagging side of 0 degrees. Dropout should occur at 97% to 98% of actual pickup.
Return Delta Angle to 0 degrees.

Step 9: With the Auxiliary Voltage set at nominal frequency, step change the frequency of the Line

voltage input by -0.25 hertz (59.75 on a 60 hertz relay). Note that OUT1 is closing and opening
based on a slip rate of 0.25 hertz. Decrease the frequency until OUT1 stays open. Slowly
increase the frequency until OUT1 begins to cycle (closed/open). Cycling pickup should occur
within

±2% of the Delta Slip setting. Also, check on the fast side (60.25 for a 60 hertz relay).

Step 10: Repeat Step 9 for the Auxiliary Voltage input.

Step 11: (Optional.) Repeat Steps 4 through 10 for Setting Group 1.

Breaker Failure (BF) (BE1-700C)

Purpose: To verify the operation of the breaker failure (BF) function.

Reference Commands: SL-BF, SP-BF

Step 1: Prepare the BF function block for testing by transmitting the commands in Table 13-66 to the

relay.

Table 13-66. BF Pickup Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE settings.

Y

Confirm overwrite.

SL-N=BF

Sets BF as custom logic name.

SL-BF=1,IN4,/IN3

Enables BF, IN4 initiate, /IN3 block.

SP-BF=50m

Set BF time delay at minimum.

SL-VO1=BFT

Enables OUT1 to close for BF trip.

SL-VO2=BFPU

Enables OUT2 to close for BF pickup.

SG-CTP=1

Sets P, N CT ratio at 1:1

SG-TRIGGER=BFT,BFPU,0

Enable BFT to log and trigger fault recording.

SG-TARG=BF

Enables BF target.

EXIT;Y

Exit and save settings.

Step 2: Energize relay Inputs IN3 and IN4. This enables the BF logic and BF initiate. The BF current

detector pickup setting is a fixed value that is determined by the relay current sensing type.
Table 13-67 lists the pickup setting for each current sensing type.

Table 13-67. BF Current Detector Pickup Settings

Sensing Type

Pickup Setting

B (1 A)

0.1 A

E or F (5 A)

0.5 A

9376700990 Rev M

BE1-700 Testing and Maintenance

13-41