Table b-10), On (table b-11) – Basler Electric BE1-700 User Manual
Page 444
Type
ASCII Command
Function
HMI
Screen
C
SL-<x>50T<p>[=<mode>,<BLK logic>]
Read/Set logic for 50 function modules.
N/A
C
SL-<x>51<p>[=<mode>,<BLK logic>]
Read/Set logic for 51 function modules.
N/A
C
SL-<x>59<p>[=<mode>,<BLK logic>]
Read/Set logic for 59 function modules.
N/A
SL-<x>62[=<mode>,<INI logic>,<BLK logic>]
Read/Set logic for 62 function modules.
N/A
O
SL-79[={mode},{RI logic},{STATUS logic},
{WAIT logic},{LOCKOUT logic}]
Read/Set logic for 79 function.
N/A
V
SL-<x>81[=<mode>,<BLK logic>]
Read/Set logic for 81 function modules.
N/A
C
SL-BF<x>[=<mode>,<INI logic>,<BLK logic>]
Read/Set logic for breaker failure
function modules.
N/A
SL-GROUP[=<mode>,<D0 logic>,<D1
logic>,<automatic>]
Read/Set logic for setting group
module.
N/A
SL-N[=<name>]
Read, set, or copy the name of the
custom logic.
N/A
SL-VO<x>[=<Boolean equation>]
Read/Set output logic.
N/A
SL-<x>43[=<mode>]
Read/Set logic for Virtual Switches.
N/A
SL-101[=<mode>]
Read/Set logic for Virtual Breaker
Control Switch.
N/A
Table B-10. User Programmable Name Setting Command
Type
ASCII Command
Function
HMI
Screen
SN[-<var>[=<name>,<TRUE label>,<FALSE
label>]]
Read/Set user programmable
names.
N/A
Table B-11. Protection Setting Commands
Type
ASCII Command
Function
HMI
Screen
S<g>
Read all protection settings.
N/A
V
S<g>-24[=<Pickup>,<Time Delay>,<Reset
Time>,<Curve>]
Read/Set 24 pickup level, time
delay, and reset delay.
5.x.1.1
V
S<g>-25[=<volts>,<ang>,<slip>,<mode>]
Read/Set 25 delta volts, phase
angle, slip frequency, and
mode.
5.x.2.1
V
S<g>-25VM[=<live volts>,<dead volts>,<time dial>,<logic
condition>]
Read/Set 25VM pickups, time
delay, and logic condition.
5.x.2.2 -
5.x.2.4
V
S<g>-<x>27<p>[=<Pickup>,<Time Delay>]
Read/Set 27 pickup level, time
delay, and mode.
5.x.3.1 -
5.x.3.3
V
S<g>-47[=<Pickup>,<Time Delay>]
Read/Set 47 pickup level and
time delay.
5.x.5.1
C
S<g>-<x>50T<p>[=<Pickup>,<Time Delay>]
Read/Set 50T pickup level and
time delay.
5.x.6.1 -
5.x.6.6
C
S<g>-<x>51<p>[=<Pickup>,<Time Delay>,<Curve>]
Read/Set 51 pickup level, time
delay, and curve.
5.x.7.1 -
5.x.7.5
V
S<g>-<x>59<p>[=<Pickup>,<Time Delay>]
Read/Set 59 pickup level, time
delay, and mode.
5.x.8.1 -
5.x.8.4
S<g>-<x>62[=<T1>,<T2>]
Read/Set 62 time delay.
5.x.9.1 -
5.x.9.2
S<g>-67N[=<Mode>,<Quantity>]
Read/Set 67 Neutral Polarizing
Mode and Quantities.
5.x.10.1 -
5.x.10.2
B-4
BE1-700 Command Cross-Reference
9376700990 Rev M