Table b-10), On (table b-11) – Basler Electric BE1-700 User Manual

Page 444

Advertising
background image

Type

ASCII Command

Function

HMI

Screen

C

SL-<x>50T<p>[=<mode>,<BLK logic>]

Read/Set logic for 50 function modules.

N/A

C

SL-<x>51<p>[=<mode>,<BLK logic>]

Read/Set logic for 51 function modules.

N/A

C

SL-<x>59<p>[=<mode>,<BLK logic>]

Read/Set logic for 59 function modules.

N/A

SL-<x>62[=<mode>,<INI logic>,<BLK logic>]

Read/Set logic for 62 function modules.

N/A

O

SL-79[={mode},{RI logic},{STATUS logic},
{WAIT logic},{LOCKOUT logic}]

Read/Set logic for 79 function.

N/A

V

SL-<x>81[=<mode>,<BLK logic>]

Read/Set logic for 81 function modules.

N/A

C

SL-BF<x>[=<mode>,<INI logic>,<BLK logic>]

Read/Set logic for breaker failure
function modules.

N/A

SL-GROUP[=<mode>,<D0 logic>,<D1
logic>,<automatic>]

Read/Set logic for setting group
module.

N/A

SL-N[=<name>]

Read, set, or copy the name of the
custom logic.

N/A

SL-VO<x>[=<Boolean equation>]

Read/Set output logic.

N/A

SL-<x>43[=<mode>]

Read/Set logic for Virtual Switches.

N/A

SL-101[=<mode>]

Read/Set logic for Virtual Breaker
Control Switch.

N/A

Table B-10. User Programmable Name Setting Command

Type

ASCII Command

Function

HMI

Screen

SN[-<var>[=<name>,<TRUE label>,<FALSE
label>]]

Read/Set user programmable
names.

N/A

Table B-11. Protection Setting Commands

Type

ASCII Command

Function

HMI

Screen

S<g>

Read all protection settings.

N/A

V

S<g>-24[=<Pickup>,<Time Delay>,<Reset
Time>,<Curve>]

Read/Set 24 pickup level, time
delay, and reset delay.

5.x.1.1

V

S<g>-25[=<volts>,<ang>,<slip>,<mode>]

Read/Set 25 delta volts, phase
angle, slip frequency, and
mode.

5.x.2.1

V

S<g>-25VM[=<live volts>,<dead volts>,<time dial>,<logic
condition>]

Read/Set 25VM pickups, time
delay, and logic condition.

5.x.2.2 -

5.x.2.4

V

S<g>-<x>27<p>[=<Pickup>,<Time Delay>]

Read/Set 27 pickup level, time
delay, and mode.

5.x.3.1 -

5.x.3.3

V

S<g>-47[=<Pickup>,<Time Delay>]

Read/Set 47 pickup level and
time delay.

5.x.5.1

C

S<g>-<x>50T<p>[=<Pickup>,<Time Delay>]

Read/Set 50T pickup level and
time delay.

5.x.6.1 -

5.x.6.6

C

S<g>-<x>51<p>[=<Pickup>,<Time Delay>,<Curve>]

Read/Set 51 pickup level, time
delay, and curve.

5.x.7.1 -

5.x.7.5

V

S<g>-<x>59<p>[=<Pickup>,<Time Delay>]

Read/Set 59 pickup level, time
delay, and mode.

5.x.8.1 -

5.x.8.4

S<g>-<x>62[=<T1>,<T2>]

Read/Set 62 time delay.

5.x.9.1 -

5.x.9.2

S<g>-67N[=<Mode>,<Quantity>]

Read/Set 67 Neutral Polarizing
Mode and Quantities.

5.x.10.1 -

5.x.10.2

B-4

BE1-700 Command Cross-Reference

9376700990 Rev M