Basler Electric BE1-700 User Manual

Page 197

Advertising
background image

Output

Purpose

Output Description

Label

State Labels

TRUE

FALSE

VO5

(OUT5)

Major Alarm

Closes contact when Major Alarm
expression is TRUE

ALMMAJ

Active

Normal

BESTlogic expression: VO5=ALMMAJ

VO6

Not used

VO6

True

False

BESTlogic expression: VO6=0

VO7

Not used

VO7

True

False

BESTlogic expression: VO7=0

VO8

Reclose Initiate

TRUE when any protective
element trips or when the external
reclose initiate input is TRUE.

RCL_INI

INI

Normal

BESTlogic expression: VO8=VO11+IN3

VO9

Recloser Drive to Lockout Drive recloser to lockout if IN2 is

energized or the high-set
instantaneous elements trip.

RCL_DTL

DTL

Normal

BESTlogic expression: VO9=150TPT+150TNT+15OTQT+/IN2

VO10

Not used

VO10

True

False

BESTlogic expression: VO10=0

VO11

Protective Trip
Expression

TRUE when any 50, 150 or 51
element has timed out.

PROT_TRIP

Trip

Normal

BESTlogic expression: VO11=50TPT+150TPT+50TNT+150TNT+50TQT+150TQT+51PT+51NT+51QT

VO12

Protection Picked Up
Expression

TRUE when any 50, 150 or 51
element has picked up.

PROT_PU

PU

Normal

BESTlogic expression:
VO12=50TPPU+150TPPU+50TNPU+150TNPU+50TQPU+150TQPU+51PPU+51NPU+51QPU

VO13

Alarm Mask 21

VO13

True

False

BESTlogic expression: VO13=0

VO14

Alarm Mask 22

VO14

True

False

BESTlogic expression: VO14=0

VO15

Alarm Mask 23

VO15

True

False

BESTlogic expression: VO15=0