Table 8-21. Miscellaneous Logic Expressions

Command

Reference


SA-RESET


Section 6, Reporting and Alarm Functions, Alarms Function


SB-DUTY


Section 6, Reporting and Alarm Functions, Breaker Monitoring


SB-LOGIC


Section 6, Reporting and Alarm Functions, Breaker Monitoring


SG-TARG


Section 6, Reporting and Alarm Functions, Fault Reporting


SG-TRIGGER


Section 6, Reporting and Alarm Functions, Fault Reporting


SP-79ZONE


Section 4, Protection and Control

APPLICATION TIPS

Output Contact Latch Using the TRSTKEY Logic Variable

On occasion, an application will call for latching an output contact such as simulating a lockout (86)
function. Each output contact of a Basler Electric relay can be set to latch by using an AND gate to seal
the trip condition and the TRSTKEY logic variable to reset the latch.

As an example, assume a BE1-700 is used for overcurrent protection of a radial transformer shown in
Figure 8-11, Station One-line Drawing. The user wants to trip and lockout the high side circuit switcher for
an overcurrent trip.

Referring to Figure 8-12, a 51 or 151 trip will causeVO11 to go high. This in turn causes VO14 to go high,
sealing the inputs of VO3 and VO4 through AND gate VO7. This allows Output Contacts 3 and 4 to
transition and remain in that state until the TRSTKEY variable is asserted. In this example, the circuit
switcher will be tripped by Output 3 (simulating an 86

Aa@) and its close circuit disabled by Output 4

(simulating an 86

Ab@). The HMI LCD display automatically goes to the Target Screen per the automatic

display priority function. When the operator presses the Reset key while the LCD display is on the Target
Screen (Reset key of the HMI is context sensitive), the TRSTKEY logic variable goes high breaking the
VO7 seal in at which point Output 3 will open and Output 4 will close. Refer to Section 6, Reporting and
Alarm Functions, Fault Reporting
.

The data in Table 8-22 include the logic settings and equations for the ARSTKEY and TRSTKEY
functions.

9376700990 Rev M

BE1-700 Application

8-31