Table 13-90. x62 mode 5 test commands -50 – Basler Electric BE1-700 User Manual

Page 346

Advertising
background image

Figure 13-3. Mode 3 (One-Shot Retriggerable) Timing Example

Mode 4 - Oscillator

Because this operating mode is not intended for general use, no testing procedure is available.
Information about Mode 4 is available in Section 4, Protection and Control, General Purpose Logic
Timers
.

Mode 5 - Integrating

Step 1: Prepare the 62 Timer for Mode 5 testing by transmitting the commands in Table 13-90.

Table 13-90. x62 Mode 5 Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE settings.

Y

Confirm overwrite.

SL-N=T62

Sets T62 as custom logic name.

SL-43=2

Enables 43 Switch ON/OFF mode.

SN-43=62_INI,PU,DO

Name Switch 43 to make SER easier to read.

SL-62=5,43,0

Enables 62 integrating mode, 43 initiate, no blocking.

S0-62=15s,5s

Sets T1 at 15 seconds. Sets T2 at 5 seconds.

EXIT;Y

Exit and save settings.

Step 2: Transmit the commands of Table 13-91 to the relay. These commands supply a block input to

the 62 Timer by changing the 43 Switch state to TRUE.

Table 13-91. x62 Mode 5 Timer Initiate Commands

Command

Purpose

A=

Gains write access.

CS-43=1

Selects 43 for TRUE operation.

CO-43=1

Executes 43 TRUE operation.

Wait no longer than 10 seconds to interrupt the T1 timer.

CS-43=0

Selects 43 for FALSE operation.

CO-43=0

Executes 43 FALSE operation.

NOTE

The CS and CO commands of Table 13-91 are performed three times. Follow the
timing sequence to illustrate timer mode action. The time delay settings may be
increased if difficulty is encountered with repeating the 43 Switch actions.

13-50

BE1-700 Testing and Maintenance

9376700990 Rev M