Table 13-25. 51p/51n/51q timing values -22, Table 13-26. 51p/51n/51q pickup test commands -22 – Basler Electric BE1-700 User Manual

Page 318

Advertising
background image

Table 13-25. 51P/51N/51Q Timing Values

Sensing

Type

Time Dial

Applied Current

Relay Trip Limits

Lower Limit

Upper Limit

1 A

0.5

0.15 Aac

0.748 s

0.827 s

0.50 Aac

0.190 s

0.240 s

2.5 Aac

0.100 s

0.150 s

5

0.15 Aac

7.244 s

8.007 s

0.50 Aac

1.798 s

1.988 s

2.5 Aac

0.944 s

1.044 s

9.9

0.15 Aac

14.318 s

15.825 s

0.50 Aac

3.535 s

3.907 s

2.5 Aac

1.844 s

2.038 s

5 A

0.5

2.5 Aac

0.190 s

0.240 s

12.5 Aac

0.100 s

0.150 s

5

0.75 Aac

7.244 s

8.007 s

2.5 Aac

1.798 s

1.988 s

12.5 Aac

0.944 s

1.044 s

9.9

0.75 Aac

14.318 s

15.825 s

2.5 Aac

3.535 s

3.907 s

12.5 Aac

1.844 s

2.038 s

Step 4: Repeat Steps 2 and 3 for all of the current and time dial settings for your current sensing type.

Step 5: (Optional.) Repeat Steps 2 through 4 for phase B (Terminals D3 and D4) and phase C

(Terminals D5 and D6).

Step 6: (Optional.) Using ASCII commands, substitute 151 for any 51 logic or setting commands in each

test.

Pickup and Dropout Verification

Purpose: To verify the pickup accuracy of the 51P, 51N, 151P, 151N, and 51Q elements.

Reference Commands: SL-51P, SL-151P, SL-51N, SL-51Q, SL-151N, SL-GROUP, SL-VO

Step 1: Connect a current source to Terminals D1 and D2 (A-phase). Refer to Figure 12-3 for

terminal locations. An ohmmeter or continuity tester may be used to monitor output contact
status.

Step 2: To prepare the 51P, 51N, and 51Q elements for testing, transmit the commands in Table 13-26

to the relay. Reset targets.

Table 13-26. 51P/51N/51Q Pickup Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE
settings.

Y

Confirm overwrite.

SL-N=PU51

Sets PU51 as custom logic name.

SL-51P=1,0

Enables 51P and disables blocking.

SL-51N=1,0

Enables 51N and disables blocking.

SL-51Q=1,0

Enables 51Q and disables blocking.

13-22

BE1-700 Testing and Maintenance

9376700990 Rev M

Advertising
This manual is related to the following products: