Table b-7), Ng (table b-8), Table b-9) – Basler Electric BE1-700 User Manual
Page 443
Table B-7. General Setting Commands
Type
ASCII Command
Function
HMI
Screen
SG
Read all general settings.
N/A
SG-BL=<time>
Read/Set the backlight timer.
6.4
SG-CLK[=<date format(M/D)>,<time
format(12/24)>]
Read/Program time and date format.
N/A
SG-COM<#>[=<baud>,A<addr>,P<pglen>,
R<reply ack>,X<XON ena>]
Read/Set serial communication protocol.
6.1.1,
6.1.3
C
SG-CT<x>[=<CT ratio>]
Read/Set Phase/Neutral CT ratio.
6.3.1 -
6.3.2
C
SG-DI<x>[=<interval>]
Read/Set P(IA/IB/IC/var/watt), N and Q
demand interval.
N/A
SG-DSP[P/N]
Read analog signal dsp filter type.
N/A
SG-EMAIL[#[={email logic}]]
Read/Enter email logic.
N/A
SG-FREQ[=<freq(Hz)>]
Read/Enter power system frequency.
6.3.8
SG-HOLD<x>[=<1/0 hold ena>]
Read/Program output hold operation.
N/A
SG-ID[=<relayID>,<stationID>]
Read/Set relay ID and station ID used in
reports.
N/A
SG-IN<x>[=<Recognition Time>,<Debounce
Time>]
Read/Set input recognition/debounce.
N/A
SG-NOM[=<nom volts>,<nom amps>]
Read/Set nominal voltage and current.
6.3.7
SG-OSC[=<# records saved>]
Read/Set the number of oscillographic
fault records saved.
N/A
SG-PHROT[=<phase rotation>]
Read/Set phase rotation setting.
6.3.9
SG-SCREEN<x>[=<default screen number>]
Read/Set default screen(s).
N/A
SG-SGCON[=<time>]
Read/Set SGC output time.
N/A
SG-TARG[=<x/x/…x>,<rst TARG logic>]
Report/Enable Target list and Reset
Target logic.
N/A
SG-TRIGGER<x>[=<TRIPtrigger>,<Putrigger>,
<LOGICtrigger>]
Read/Set trigger logic.
N/A
V
SG-VTP[=<VT ratio>,<connection>,
<27/59 mode>,<51/27R mode>]
Read/Set VT ratio, connection, and 27/59
pickup mode.
6.3.3 -
6.3.4
V
SG-VTX[=<VT_ratio>,<connection>]
Read/Set Aux. VT ratio and connection.
6.3.5 -
6.3.6
Table B-8. Breaker Monitoring and Setting Commands
Type
ASCII Command
Function
HMI Screen
C
SB
Read all breaker settings.
N/A
C
SB-DUTY[=<mode>,<DMAX>]
Read/Set breaker contact duty.
N/A
C
SB-LOGIC[=<breaker close logic>]
Read/Set breaker contact logic.
N/A
Table B-9. Programmable Logic Setting Commands
Type
ASCII Command
Function
HMI
Screen
SL[:<name>]
Obtain setting logic information.
N/A
V
SL-24[=<mode>,<BLK logic>]
Read/Set logic for 24 function modules.
N/A
V
SL-25[=<mode>,<BLK logic>]
Read/Set logic for 25 function modules.
N/A
V
SL-<x>27<p>[=<mode>,<BLK logic>]
Read/Set logic for 27 function modules.
N/A
V
SL-47[=<mode>,<BLK logic>]
Read/Set logic for 47 function modules.
N/A