Table B-7. General Setting Commands

Type

ASCII Command

Function

HMI

Screen

SG

Read all general settings.

N/A

SG-BL=<time>

Read/Set the backlight timer.

6.4

SG-CLK[=<date format(M/D)>,<time
format(12/24)>]

Read/Program time and date format.

N/A

SG-COM<#>[=<baud>,A<addr>,P<pglen>,
R<reply ack>,X<XON ena>]

Read/Set serial communication protocol.

6.1.1,

6.1.3

C

SG-CT<x>[=<CT ratio>]

Read/Set Phase/Neutral CT ratio.

6.3.1 -

6.3.2

C

SG-DI<x>[=<interval>]

Read/Set P(IA/IB/IC/var/watt), N and Q
demand interval.

N/A

SG-DSP[P/N]

Read analog signal dsp filter type.

N/A

SG-EMAIL[#[={email logic}]]

Read/Enter email logic.

N/A

SG-FREQ[=<freq(Hz)>]

Read/Enter power system frequency.

6.3.8

SG-HOLD<x>[=<1/0 hold ena>]

Read/Program output hold operation.

N/A

SG-ID[=<relayID>,<stationID>]

Read/Set relay ID and station ID used in
reports.

N/A

SG-IN<x>[=<Recognition Time>,<Debounce
Time>]

Read/Set input recognition/debounce.

N/A

SG-NOM[=<nom volts>,<nom amps>]

Read/Set nominal voltage and current.

6.3.7

SG-OSC[=<# records saved>]

Read/Set the number of oscillographic
fault records saved.

N/A

SG-PHROT[=<phase rotation>]

Read/Set phase rotation setting.

6.3.9

SG-SCREEN<x>[=<default screen number>]

Read/Set default screen(s).

N/A

SG-SGCON[=<time>]

Read/Set SGC output time.

N/A

SG-TARG[=<x/x/…x>,<rst TARG logic>]

Report/Enable Target list and Reset
Target logic.

N/A

SG-TRIGGER<x>[=<TRIPtrigger>,<Putrigger>,
<LOGICtrigger>]

Read/Set trigger logic.

N/A

V

SG-VTP[=<VT ratio>,<connection>,
<27/59 mode>,<51/27R mode>]

Read/Set VT ratio, connection, and 27/59
pickup mode.

6.3.3 -

6.3.4

V

SG-VTX[=<VT_ratio>,<connection>]

Read/Set Aux. VT ratio and connection.

6.3.5 -

6.3.6

Table B-8. Breaker Monitoring and Setting Commands

Type

ASCII Command

Function

HMI Screen

C

SB

Read all breaker settings.

N/A

C

SB-DUTY[=<mode>,<DMAX>]

Read/Set breaker contact duty.

N/A

C

SB-LOGIC[=<breaker close logic>]

Read/Set breaker contact logic.

N/A

Table B-9. Programmable Logic Setting Commands

Type

ASCII Command

Function

HMI

Screen

SL[:<name>]

Obtain setting logic information.

N/A

V

SL-24[=<mode>,<BLK logic>]

Read/Set logic for 24 function modules.

N/A

V

SL-25[=<mode>,<BLK logic>]

Read/Set logic for 25 function modules.

N/A

V

SL-<x>27<p>[=<mode>,<BLK logic>]

Read/Set logic for 27 function modules.

N/A

V

SL-47[=<mode>,<BLK logic>]

Read/Set logic for 47 function modules.

N/A

9376700990 Rev M

BE1-700 Command Cross-Reference

B-3