Auxiliary voltage input verification - vx and vx 3, Fundamental and third harmonic) (be1-700v), Table 13-4. voltage circuit verification values -7 – Basler Electric BE1-700 User Manual

Page 303: Values -7

Advertising
background image

Step 4: Connect relay Terminals C13 (A-phase), C14 (B-phase), and C15 (C-phase) together. Connect

an ac voltage source at nominal frequency to the three jumpered terminals and the Neutral
Terminal (C16).

Step 5: Apply the voltage values listed in Table 13-4 and verify voltage measuring accuracy by

transmitting the M command to the relay. HMI Screen 3.1 can also be monitored to verify
voltage measurements or the Metering screen of BESTCOMS.

Table 13-4. Voltage Circuit Verification Values

Applied Voltage

Measured Voltage

Lower Limit

Upper Limit

80 volts

79.2 V

80.8 V

100 volts

99.0 V

101.0 V

120 volts

118.8 V

121.2 V

140 volts

138.6 V

141.4 V

160 volts

156.8 V

163.2 V

Auxiliary Voltage Input Verification - VX and VX 3

rd

(Fundamental and Third Harmonic) (BE1-700V)

Step 1: Connect relay Terminals C17 (polarity) and C18 to a 60 hertz ac voltage source.

Step 2: Apply the voltage values listed in Table 13-5 and verify voltage-measuring accuracy by

transmitting the M-V command to the relay. BESTCOMS Metering or HMI Screens 3.3 can also
be monitored to verify VX voltage measurements.

Step 3: Connect relay Terminals C17 (polarity) and C18 to a 180-hertz (third harmonic) ac voltage

source.

Step 4: Apply the voltage values listed in Table 13-5 and verify voltage-measuring accuracy by

transmitting the M command to the relay. BESTCOMS Metering or HMI Screen 3.3 can also be
monitored to verify VX voltage measurements.

Table 13-5. Aux Voltage Circuit Verification VX & VX 3

rd

Values

Applied Voltage

Measured Voltage

Lower Limit

Upper Limit

5 Vac

4.95 Vac

5.05 Vac

20 Vac

19.8 Vac

20.2 Vac

60 Vac

59.4 Vac

60.6 Vac

80 Vac

79.2 Vac

80.8 Vac

120 Vac

118.8 Vac

121.2 Vac

Line and Bus Angle, Frequency, and Slip Verification

• Connect relay Terminals C13 (polarity) and C16 (A to Neutral of the three-phase voltage input) to

a 60-hertz ac voltage source (line voltage).

• Connect relay Terminals C17 (polarity) and C18 (auxiliary voltage input) to a second 60-hertz ac

voltage source (bus voltage).

• Apply 115 volts at 0 degrees and 60 hertz to both sources. Verify the measuring accuracy of the

line and bus frequency, angle between the two voltages and slip frequency by transmitting the M
command to the relay. HMI Screens 3.10 and 3.11 can also be monitored to verify the
measurements.

• Vary the angle of the line voltage and verify the measured angle as in Step 3. Polarity of the

angle measurement is relative to the angle of the line voltage. That is, if the line voltage lags the

9376700990 Rev M

BE1-700 Testing and Maintenance