Table 7-1. Logic Variable Names and Descriptions

Variable

Name

Description

Variable

Name

Description

Inputs and Outputs

59XPU

59 Auxiliary Overvoltage Picked Up

IN1-IN4

Inputs 1 through 4 Status

159PT

159 Phase Overvoltage Tripped

VOA

Relay Trouble Alarm Output Status

159PPU

159 Phase Overvoltage Picked Up

VO1-VO5

Virtual Outputs 1 through 5 (hardware outputs)

159XT

159 Auxiliary Overvoltage Tripped

VO6-VO15

Virtual Outputs 6 through 15

159XPU

159 Auxiliary Overvoltage Picked Up

Controls

47PU

47 Negative Sequence Picked Up

TRSTKEY

HMI Target Reset Key

47T

47 Negative Sequence Tripped

ARSTKEY

HMI Alarm Reset Key

Over/Under Frequency

101T

Virtual Breaker Control Switch Tripped

81T

81 Tripped

101C

Virtual Breaker Control Switch Closed

181T

181 Tripped

101SC

Virtual Breaker Control Switch Slip Contact

281T

281 Tripped

62

62 Timer Output

381T

381 Tripped

162

162 Timer Output

481T

481 Tripped

43

Virtual Switch 43 Output

581T

581 Tripped

143

Virtual Switch 143 Output

Breaker Failure (BE1-700C only)

SG0

Setting Group 0 Active (default)

BFT

Breaker Failure Tripped

SG1

Setting Group 1 Active

BFPU

Breaker Failure Picked Up

Alarms and Monitor

Instantaneous Overcurrent (BE1-700C only)

ALMLGC

Logic Alarm

50TPT

50T Phase Tripped

ALMMAJ

Major Alarm

50TPPU

50T Phase Picked Up

ALMMIN

Minor Alarm

50TNT

50T Neutral Tripped

OUT1MON

Output 1 Monitor (circuit continuity)

50TNPU

50T Neutral Picked Up

Reclosing (Optional)

50TQT

50T Negative-Sequence Tripped

79C

79 Close Signal

50TQPU

50T Negative-Sequence Picked Up

79RNG

79 Running/Block Tap Changer

150TPT

150T Phase Tripped

79LO

79 Lockout

150TPPU

150T Phase Picked Up

79RST

79 Reset

150TNT

150T Neutral Tripped

79P

79 Pilot

150TNPU

150T Neutral Picked Up

79SCB

79 Sequence Control Block

150TQT

150T Negative-Sequence Tripped

Voltage (BE1-700V only)

150TQPU

150T Negative-Sequence Picked Up

24T

24 Overexcitation Tripped

Time Overcurrent (BE1-700C only)

24PU

24 Overexcitation Picked Up

51PT

51 Phase Tripped

25

25 Sync-Check Output

51PPU

51 Phase Picked Up

25VM1

25 Voltage Monitor 1

51NT

51 Neutral Tripped

27PT

27 Phase Undervoltage Tripped

51NPU

51 Neutral Picked Up

27PPU

27 Phase Undervoltage Picked Up

51QT

51 Negative-Sequence Tripped

127PT

127 Phase Undervoltage Tripped

51QPU

51 Negative-Sequence Picked Up

127PPU

127 Phase Undervoltage Picked Up

151PT

151 Phase Tripped

27XT

27 Auxiliary Undervoltage Tripped

151PPU

151 Phase Picked Up

27XPU

27 Auxiliary Undervoltage Picked Up

151NT

151 Neutral Tripped

59PT

59 Phase Overvoltage Tripped

151NPU

151 Neutral Picked Up

59PPU

59 Phase Overvoltage Picked Up

Fuse Loss (BE1-700V only)

59XT

59 Auxiliary Overvoltage Tripped

60FL

60 Loss of Potential Alarm

9376700990 Rev M

BE1-700 BESTlogic Programmable Logic

7-5