SG-VTX Command (BE1-700V)
Purpose:

Read/Set Aux VT ratio and connection

Syntax:

SG-VTX[={VTratio},{connection}]

Example:

SG-VTX or VTX=10,AB or VTX=1200:120,GR or VTX=1200/120,AN

Reference:

Section 3, Input and Output Functions, Power System Inputs

Programmable Logic Setting Commands

SL Command
Purpose:

Obtain Setting Logic Information

Syntax:

SL:[{name}]

Example:

SL, SL: or SL:BASIC-OC

Reference:

Section 11, ASCII Command Interface, Settings (S) Command Descriptions

SL-24 Command (BE1-700V only)
Purpose:

Read/Set Logic for 24 Function Modules

Syntax:

SL-24[={mode},{BLK logic}]

Example:

SL-24 or SL-24=1,0 or SL-24=1,IN3

Reference:

Section 4, Protection and Control, Voltage Protection

SL-25 Command (BE1-700V only) (Optional)
Purpose:

Read/Set Logic for 25 Function Modules

Syntax:

SL-25[={mode},{BLK logic}]

Example:

SL-25 or SL-25=1,0 or SL-25=1,IN3

Reference:

Section 4, Protection and Control, Synchronism-Check Protection

SL-27 Command (BE1-700V only)
Purpose:

Read/Set Logic for 27 Function Modules

Syntax:

SL-{x}27[{p}[={mode},{BLK logic}]] where x=blank/1, p=P/X

Example:

SL-27 or SL-27P=1,0 or SL-27X=3,0 or SL-127P=1,IN3

Reference:

Section 4, Protection and Control, Voltage Protection

SL-43 Command
Purpose:

Read/Set Logic for Virtual switch (x43)

Syntax:

SL-{x}43[=mode] where x = blank/1/2/3, mode=0/1/2/3

Example:

SL-43 or SL-43=0 or SL-143=1

Reference:

Section 4, Protection and Control, Virtual Switches

SL-47 Command (BE1-700V only)
Purpose:

Read/Set Logic for 47 Function Modules

Syntax:

SL-47[={mode},{BLK logic}]

Example:

SL-47 or SL-47=1,0 or SL-47=1,IN3

Reference:

Section 4, Protection and Control, Voltage Protection

SL-50T Command (BE1-700C only)
Purpose:

Read/Set Logic for x50 Function Modules

Syntax:

SL-{x}50T[{p}[={mode},{BLK logic}]] where x = blank/1 and p = P/N/Q

Example:

SL-50T or SL-50T=1,0 or SL-150TN=1,IN3

Reference:

Section 4, Protection and Control, Overcurrent Protection

SL-51 Command (BE1-700C only)
Purpose:

Read/Set Logic for 51 Function Modules

Syntax:

SL-51[{p}[={mode},{BLK logic}]] where p=P/N

Example:

SL-51 or SL-51P=1,0 or SL-51N=1,IN3 or SL-151N=1,0

Reference:

Section 4, Protection and Control, Overcurrent Protection

9376700990 Rev M

BE1-700 ASCII Command Interface

11-17