Clock, Irig port, Setting the clock function – Basler Electric BE1-700 User Manual

Page 134: Clock -2, Irig port -2, Setting the clock function -2

Advertising
background image

CLOCK

The BE1-700 provides a real-time clock that is used by the demand reporting function, the fault reporting
function, the oscillograph recording function, and the sequence of events recorder function to time-stamp
events. The clock function records the year in two-digit format.

IRIG Port

IRIG time code signal connections are located on the rear panel. When a valid time code signal is
detected at the port, it is used to synchronize the clock function. Note that the IRIG time code signal does
not contain year information. For this reason, it is necessary to enter the date even when using an IRIG
signal. Year information is stored in nonvolatile memory so that when operating power is restored after an
outage and the clock is re-synchronized the current year is restored. When the clock rolls over to a new
year, the year is automatically incremented in nonvolatile memory. An alarm bit is included in the
programmable alarm function for loss of IRIG signal. The alarm point monitors for IRIG signal loss once a
valid signal is detected at the IRIG port.

The IRIG input is fully isolated and accepts a demodulated (dc level-shifted) signal. The input signal must
be 3.5 volts or higher to be recognized as a valid signal. Maximum input signal level is +10 to -10 volts
(20-volt range). Input resistance is nonlinear and rated at 4 k

Ω at 3.5 volts.

Setting the Clock Function

Time and date format settings are made using BESTCOMS. Figure 6-2 illustrates the BESTCOMS screen
used to select time and date format settings. To open the screen, select Reporting and Alarms from the
Screens pull-down menu. Then select the Clock Display Mode tab. Alternately, settings may be made
using the SG-CLK ASCII command. Refer to Table 6-2, Time and Date Format Settings.

Figure 6-2. Reporting and Alarms Screen, Clock Display Mode Tab

Time and date reporting can be displayed in 12 or 24-hour format. When operating in the 12-hour format,
the A.M./P.M. parameter is placed between the minutes and seconds parameters (10:24P23.004
indicates 10:24 in the evening). The default time format is 24 hours. Date reporting format can display the
date in mm/dd/yy or dd/mm/yy format. The default date format is mm/dd/yy. The relay clock can also
accommodate daylight saving time changes. Automatic daylight saving time adjustments are optional and
are disabled by default.

6-2

BE1-700 Reporting and Alarm Functions

9376700990 Rev M