Reduced switching losses through switching frequency reduction
The advantage of a switching frequency reduction are the reduced switching losses in the

controller, which are monitored via an I x t evaluation.

• A reduced switching frequency enables a greater current-time area at the output than it would

be the case with a higher switching frequency. However, depending on the process, you always

have to make a compromise between the torque ripple and the output power.

5.5.2

Monitoring of the device utilisation

In

C00064

the device utilisation (I x t) is displayed over the last 180 seconds in [%].

• If the value displayed in

C00064

exceeds the warning threshold set in

C00123

, the error

message "device utilisation Ixt > C00123" is output and the fault response set in

C00604

occurs

(default setting: "Warning").

• If the value displayed in

C00064

exceeds 100 %, the error message "device utilisation Ixt

> 100 %" is output and the "Fault" error response occurs.

• The fault can only be reset if the value displayed in

C00064

is < 95 % again.