2 write parameters, Write parameters, 10 "can on board" system bus – Lenze E94AxPExxxx User Manual

Page 363

Advertising
background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

363

10

"CAN on board" system bus

10.7

Parameter data transfer

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.7.3.2

Write parameters

Task: The rated current of the connected motor with I

rated

= 10.2 A (code

C00088

) is to be entered in

the controller.

Telegram to drive

Response telegram from drive (if data have been correctly transmitted)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6. byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x0602

0x23

0xA7

0x5F

0x00

0x66

0x00

0x03

0x00

Explanations on the telegram to the drive
Identifier

= 1536 + node address = 1536 + 2 = 1538 = 0x0602

(1536 = SDO1 basic identifier to the controller)

Command

= 0x23 = "Write request" (write request of a parameter to the controller)

Index

= 24575 - code number = 24575 - 88 = 24487 = 0x5FA7

Subindex

= 0 (code

C00088

does not have any subcodes)

Data 1 ... 4

= 10,2 x 10 = 102 = 0x00030066

(Value for motor current, data type U32; display factor 1/10)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6. byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x0582

0x60

0xA7

0x5F

0x00

0x00

0x00

0x00

0x00

Explanations on the telegram from the drive
Identifier

= 1408 + node address = 1408 + 2 = 1410 = 0x0582

(1408 = SDO1 basic identifier from the controller)

Command

= 0x60 = "Write response" (Acknowledgement of the write access from the controller)

Index

as in telegram to the drive

Subindex