C01121 | sync cycle time, C01122 | sync phase position, C01123 | sync tolerance – Lenze E94AxPExxxx User Manual

Page 855: C01121, C01122, C01123, Time, Into t, Position, E is increased

Advertising
background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

855

15

Parameter reference

15.2

Parameter list | C01121

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01121

C01122

C01123

Parameter | Name:

C01121 | Sync cycle time

Data type: UNSIGNED_32

Index: 23454

d

= 5B9E

h

Time interval at which the phase control loop (PLL) in the controller expects the synchronisation signals.

• The time interval set must correspond to the cycle of the synchronisation source.

Note: For synchronisation via the system bus (CANopen), only integer multiples of 1000 μs should be set.

Example: For the system bus, the interval between two synchronisation signals is set to 2 ms. If the system bus is to

be used as the synchronisation source, a synchronisation cycle of 2000 μs must be set in C01121.

"CAN on board" system bus: sync telegram

Setting range

(min. value | unit | max. value)

Lenze setting

250

μs

20000 1000 μs

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C01122 | Sync phase position

Data type: UNSIGNED_32

Index: 23453

d

= 5B9D

h

The phase position defines the zero point of time for the application relating to the synchronisation signal (bus

cycle). Since PDO processing is integrated in the system part of the application, the instant of the PDO acceptance

also changes if the phase position is changed.

• If 0 is set, the application is started together with the synchronisation signal.

• If a value > 0 is set, the application starts by the set time interval before the synchronisation signal arrives (the

phase position acts negatively).

Example: If the phase position is set to 400 μs, the system part of the application starts 400 μs before the

synchronisation signal arrives.

The effect of the sync phase position can be affected by the application cycle set in

C01130

. For the Lenze setting of

C01130

the behaviour remains as before.

"CAN on board" system bus: sync telegram

Setting range

(min. value | unit | max. value)

Lenze setting

0

μs

64000 400 μs

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C01123 | Sync tolerance

Data type: UNSIGNED_32

Index: 23452

d

= 5B9C

h

Time slot for monitoring the synchronisation signal via the LS_SyncInput system block

• If the last synchronisation signal amounted to approx. the expected value within this time slot, the

SYNC_bSyncInsideWindow output of the LS_SyncInput system block is set to TRUE.

• This setting does not affect the synchronisation process.

"CAN on board" system bus: sync telegram

Setting range

(min. value | unit | max. value)

Lenze setting

0

μs

1000 0 μs

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1