12 basic drive functions – Lenze E94AxPExxxx User Manual

Page 470

Advertising
background image

12

Basic drive functions

12.6

Homing

470

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Mode 4: pos. direction - reversing to home mark - to TP

Procedures:

Case 1:

Axis has not yet activated the reference switch:

1. Movement in positive direction with profile data set 1.
2. Reversing with positive edge at HM_bHomingMark and simultaneous activation of the profile

data set 2 for further reference search.

3. Negative edge at HM_bHomingMark enables home position detection.
4. The following positive edge of the encoder zero pulse/touch probe sensor sets the reference.
5. Absolute positioning to target position (

C02643

) with profile data set 2 (if

C02641

= "0").

Case 2:

Axis already stands on the reference switch:

1. Movement in negative direction with profile data set 2.
2. Negative edge at HM_bHomingMark enables home position detection.
3. The following positive edge of the encoder zero pulse/touch probe sensor sets the reference.
4. Absolute positioning to target position (

C02643

) with profile data set 2 (if

C02641

= "0").

 Touch probe/zero pulse

 Reference switch

1

2

0