Motor interface

6.5

Sensorless vector control (SLVC)

222

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.5.3.2

Optimising the speed controller

To optimise the speed controller, the drive must be accelerated in the base speed range with slow

setpoint ramps (e.g. acceleration time = 5 s) to speed values below the rated speed and then

decelerated again.

Gain optimisation
The proportional gain Vp is selected under

C00070

:

1. Increase

C00070

until the drive oscillates slightly (see picture

[6-11]

).

2. Reduce

C00070

until the drive runs stable again (see picture

[6-12]

).

3. Reduce

C00070

to approx. half the value.

Optimise the reset time
The reset time Tn is selected under

C00071

:

1. Reduce

C00071

until the drive oscillates slightly.

2. Increase

C00071

until the drive is stable again.

3. Increase

C00071

to approx. double the value.