Motor interface

6.3

Adjusting motor and controller to each other

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Motor reference speed
In

C00011

the reference speed of the motor must be set.

Maximum current
In

C00022

the required maximum current must be set.

• To avoid that the motor starts unintentionally without adjusting the plant data, the maximum

current in the Lenze setting is set to "0 A" in

C00022

.

Ultimate motor current I

ULT

C00620

serves to check the set ultimate motor current I

ULT

.

The ultimate motor current I

ULT

is a limit value to protect the motor from destruction or influence

of the rated data.

• This limit value must not be travelled cyclically in the drive process.
• The maximum current parameterisable in

C00022

should have a sufficient distance from this

limit value.

• If the instantaneous value of the motor current exceeds the limit value set in

C00620

the

response set in

C00619

is executed for motor protection (Lenze setting: Fault).

Maximum motor speed
Adapt the maximum motor speed in

C00596

and select the error response required when this speed

limit has been reached in

C00607

.

Note!

From the perspective of the application it has to be ensured that a maximum of 100 %

of the reference speed set in

C00011

is requested as speed setpoint.

Note!

When you select a Lenze motor from the catalogue and transfer the plant parameters of

the motor to the controller, the setting in

C00620

is automatically adjusted to the

selected motor.