"CAN on board" system bus

10.6

Process data transfer

352

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Sync phase position
The phase position defines the zero point of time for the application relating to the synchronisation

signal (bus cycle). Since PDO processing is integrated in the system part of the application, the

instant of the PDO acceptance also changes if the phase position is changed.

• If 0 is set, the application is started together with the synchronisation signal.
• If a value > 0 is set, the application starts by the set time interval before the synchronisation

signal arrives (the phase position acts negatively).

Example: If the phase position is set to 400 μs, the system part of the application starts 400 μs

before the synchronisation signal arrives.

Sync tolerance
Time slot for monitoring the synchronisation signal via the system block LS_SyncInput.

System

block "LS_SyncInput"

( 404)

• If the last synchronisation signal amounted to approx. the expected value within this time slot,

the SYNC_bSyncInsideWindow output of the LS_SyncInput system block is set to TRUE.

• This setting does not affect the synchronisation process.

Sync PLL increment
If the cycle times of the synchronisation signal and the phase-locking loop (PLL) differ from each

other, the setting in

C01124

defines the increment with which the phase-locking loop can be reset.

• The recommended reset time for the system bus as synchronisation source with regard to

occurring deviations is 109 ns (Lenze setting).

Note!

The effect of the sync phase position can be affected by the application cycle set in

C01130

. For the Lenze setting of

C01130

the behaviour remains as before.