Basic drive functions

12.9

Speed follower

530

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.9.4

Activating setpoint interface

Preconditions

• The controller is in the "Operation" device state.
• The basic function "Speed follower" is part of the active application.
• No other basic function is active.

Activation
To request the control via the basic function, the SF_bEnable enable input in the application must

be set to TRUE.

• If no other basic function is active, a change-over to the "Speed follower active" function state

is carried out, and the motor control is automatically switched over to speed control with torque

limitation. Setpoints can now be defined via the corresponding inputs.

Signal flow

• A successful change to the function state "Speed follower active" is displayed by a TRUE signal

at the SF_bEnabled status output.

Deactivation
When the SF_bEnable enable input is reset to FALSE, the setpoint inputs are inhibited. If the drive is

not at standstill, it is braked to standstill within the deceleration time set for stop unless another

basic function takes over the control of the drive.

• The status output SF_bEnabled is reset to FALSE and a change-over from the active "Speed

follower active" function state via the "Drive is stopped" function state back to the basic state

"Drive at standstill" is carried out.

Stop!

The basic function does not take over the control of the drive from the current speed, but

immediately with the setpoint defined, which may cause a jerk!