6motor interface – Lenze E94AxPExxxx User Manual

Page 275

Advertising
background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

275

6

Motor interface

6.9

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.9.4.2

Checking the individual motor phases before operation is started

A check via test signal application has been added. It injects a current into the machine before the

actual operation is started, by means of which both a motor phase failure and the existence of the

motor are checked. Only after the check has been carried out successfully, the actual operation is

continued.

• The setpoint current amplitude corresponds to the lower of the two following values:

• The test signal application is activated directly after controller enable if the following conditions

are fulfilled:

• In

C00597

a response other than "No response" is set.

• No test mode is activated (

C00398

= 0).

• No identification of pole position is active

(by device command

C00002

= "51" or "52").

• No identification procedure is active

(by device command

C00002

= "71" or "72").

• The check actuates the response set in

C00597

if one or more motor phase currents have not

reached a certain threshold value within 5 ms after controller enable.

• The threshold value depends on the device power and cannot be parameterised.
• If only one motor phase current does not reach the threshold value, "Motor phase U/V/W not

available" is entered in the logbook.

• If several motor phases do not reach the threshold value, the motor is considered as not

connected, and "Motor not connected" is entered in the logbook.

• The check is completed successfully if all three motor phase currents have exceeded the

threshold value. Then the actual operation is continued immediately.

or

Note!

• As the check is cancelled immediately if all three motor phase currents have exceeded

the threshold value, the setpoint current usually is not achieved.

• In order to be able to achieve the threshold value used for the check, the rated motor

current must at least be 10 % of the maximum device current.

• This monitoring is independent of the further rotation of the commutation angle.

50 %

2 Rated device current

50 %

2 Rated motor current

Advertising