10

"CAN on board" system bus

10.2

Possible settings by DIP switch

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.2.2

Setting the baud rate

The baud rate can be set via code

C00351

or with the DIP switches a to d:

Tip!
The baud rate resulting from the setting of the DIP switches at the last mains switching is

displayed in

C00349/2

.

Switch positions

Baud rate

d

c

b

O

OFF

ON

ON

OFF

10 kbps

OFF

ON

OFF

ON

20 kbps

OFF

OFF

ON

ON

50 kbps

OFF

OFF

ON

OFF

125 kbps

OFF

OFF

OFF

ON

250 kbps

OFF

OFF

OFF

OFF

500 kbps

ON

ON

ON

OFF

800 kbps

OFF

ON

OFF

OFF

1 Mbps

OFF

ON

ON

ON

Automatic recognition