0x008c0013, 0x008c0011, 0x008c000f – Lenze E94AxPExxxx User Manual

Page 706: 0x008c0012, 0x008c0010, 14 diagnostics & fault analysis

Advertising
background image

14

Diagnostics & fault analysis

14.7

Error messages of the operating system

706

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

MXI1: PROFIBUS module is missing or incompatible [0x008c000f]

MXI2: PROFIBUS module is missing or incompatible [0x008c0010]

MXI1: Ethernet module is missing or incompatible [0x008c0011]

MXI2: Ethernet module is missing or incompatible [0x008c0012]

MXI1: Digital frequency module is missing or incompatible [0x008c0013]

Module ID (decimal)

Error ID (decimal)

140: Application project manager

15

Response (Lenze setting printed in bold)

Setting:

C00615/2

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

E94AYCPM communication module (PROFIBUS) in

module slot MXI1 is incompatible with the application.

Use communication module supported by the

application.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

16

Response (Lenze setting printed in bold)

Setting:

C00615/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

E94AYCPM communication module (PROFIBUS) in

module slot MXI2 is incompatible with the application.

Use communication module supported by the

application.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

17

Response (Lenze setting printed in bold)

Setting:

C00615/2

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

E94AYCEN communication module (Ethernet) in module

slot MXI1 is incompatible with the application.

Use communication module supported by the

application.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

18

Response (Lenze setting printed in bold)

Setting:

C00615/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

E94AYCEN communication module (Ethernet) in module

slot MXI2 is incompatible with the application.

Use communication module supported by the

application.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

19

Response (Lenze setting printed in bold)

Setting:

C00615/2

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Digital frequency extension module in module slot MXI1

is incompatible with the application.

Use extension module supported by the application.