Basic drive functions

12.12

Brake control

572

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.12.5.1 Behaviour in case of pulse inhibit

In case of pulse inhibit the brake is applied. This occurs according to the parameter setting in

C02582

either immediately (default setting) or delayed when the threshold set for brake activation

is fallen below, which can be selected to protect the brake if high centrifugal masses occur.

Activate the brake in any case
When

C02582

= "0", the brake is immediately triggered to close to prevent the mechanics from

being damaged.

Note!

Setting the pulse inhibit results causes the motor to coast down in a load-controlled

manner until pulse enable is carried out again.
Pulse inhibit can be set in the enabled controller, e.g. due to a DC overvoltage, DC

undervoltage or the "Safe torque off" request.

Stop!

Before setting the parameters of

C02582

it is important to assess the energy conditions

of the machine.
The amount of energy stored in the machine can exceed the permissible switching

energy of a motor holding brake at the time of pulse inhibit and can thus destroy the

brake when being applied!