I-1400

Communication parameter for receiving process data via RPDO1

[10-25] Data telegram assignment

How to change the identifier:

1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").

Index:

I-1400

Name:

RPDO1 communication parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

5

- (read access only)

ro

U8

1: COB-ID used by RPDO

0x200 + node ID

0

4294967295 rw

U32

2: Transmission type

254

0

255 rw

U8

3: Inhibit time

-

- (not used for RPDOs)

rw

U16

4: Compatibility entry

-

- (reserved, read or write access leads to error message

0x06090011)

rw

U8

5: Event timer

-

- (not used for RPDOs)

rw

U16

Subindex

Meaning

Lenze code

1

RPDO1 identifier

• The basic setting is according to the "Predefined

Connection Set": Identifier = 0x200 + node ID

C00321/1

2

RPDO Transmission type according to DS301 V4.02

Transmission type ( 348)

C00323/1

8th byte

7th byte

6. byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

0/1

0/1

Extended identifier*

11-bit identifier

* The extended identifier is not supported. Bit 11 ... bit 29 must be set to "0".

Bit

Setting

Bit 30

0 RTR to this PDO possible (cannot be set).
1 RTR to this PDO not possible (Lenze).

Bit 31

0 PDO active
1 PDO inactive