C00059 | motor - number of pole pairs, C00060 | rotor position, C00061 | heatsink temperature – Lenze E94AxPExxxx User Manual

Page 762: C00062 | temperature inside the controller, C00063 | motor temperature, C00064 | device utilisation (ixt), C00064, C00059, C00060, C00063

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00059

762

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00059

C00060

C00061

C00062

C00063

C00064

Parameter | Name:

C00059 | Motor - number of pole pairs

Data type: UNSIGNED_32

Index: 24516

d

= 5FC4

h

Display range

(min. value | unit | max. value)

0

200

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00060 | Rotor position

Data type: INTEGER_32

Index: 24515

d

= 5FC3

h

Display range

(min. value | unit | max. value)

0

2047

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00061 | Heatsink temperature

Data type: INTEGER_32

Index: 24514

d

= 5FC2

h

Display range

(min. value | unit | max. value)

-200

°C

200

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00062 | Temperature inside the controller

Data type: INTEGER_32

Index: 24513

d

= 5FC1

h

Display range

(min. value | unit | max. value)

-200

°C

200

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00063 | Motor temperature

Data type: INTEGER_32

Index: 24512

d

= 5FC0

h

Motor temperature monitoring

Display range

(min. value | unit | max. value)

-200

°C

200

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00064 | Device utilisation (Ixt)

Data type: UNSIGNED_32

Index: 24511

d

= 5FBF

h

Device utilisation during the last 180 seconds

• C00064 > 100 % activates error (OC5).

• Error reset only possible if C00064 < 95 %.

Display range

(min. value | unit | max. value)

0

%

250

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1