7 limited increment for manual jog, 12 basic drive functions – Lenze E94AxPExxxx User Manual

Page 550

Advertising
background image

12

Basic drive functions

12.11

Limiter

550

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Priorisation of the limited speeds

• If several limited speeds are requested at the same time, the lowest speed with the greatest

deceleration and the lowest S-ramp time is approached from the parameters of the requested

limited speeds.

12.11.2.7 Limited increment for manual jog

Via

C02713

the maximum permissible distance (limited increment) for the basic function "

Manual

jog

" can be set.

• The request "Limited increment" is effected via the input LIM_dwControl, generally by the

control word of the safety module. If no safety module is available, the control word for the

input LIM_dwControl can also be generated by means of an inverter.

• In

C02714

the maximum permissible distance in [increments] is displayed.