10.2

Possible settings by DIP switch

The DIP switches on the front of the memory serve to set the baud rate and the node address.

[10-1] DIP switch

10.2.1

Setting the node address

The node address can be set via code

C00350

or with the DIP switches 1 to 64.

• The labelling on the housing corresponds to the values of the individual DIP switches for

determining the node address.

• Valid address range: 1 … 127

Example: Setting of the node address 23

Tip!
The node address resulting from the setting of the DIP switches at the last mains switching

is displayed in

C00349/1

.

Baud

CAN Address

O

N

c

d

b

a

64

32

16

8

4

2

1

Note!

• The addresses of the nodes must differ from each other.
• All twelve DIP switches = OFF (Lenze setting):

• At switching on, the settings under code

C00350

(node address) and

C00351

(baud

rate) will become active.

• Switch the voltage supply of the basic device off and then on again to activate altered

settings.

DIP switch

64

32

16

8

4

2

1

Switch position

OFF

OFF

ON

OFF

ON

ON

ON

Value

0

0

16

0

4

2

1

Node address

= Sum of the values = 16 + 4 + 2 + 1 = 23