5 maximum current monitoring, Maximum current monitoring, 6motor interface – Lenze E94AxPExxxx User Manual
Page 276
6
Motor interface
6.9
Monitoring
276
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.9.5
Maximum current monitoring
The ultimate motor current I
ULT
is a limit value to protect the motor
from destruction or influence of the rated data.
• This limit value must not be travelled cyclically in the drive process.
• The maximum current parameterisable in
should have a sufficient distance from this
limit value.
• If the instantaneous value of the motor current exceeds the limit value set in
the
response set in
is executed for motor protection (Lenze setting: Fault).
Note!
When you select a Lenze motor from the catalogue and transfer the plant parameters of
the motor to the controller, the setting in
is automatically adjusted to the
selected motor.