Mode 1014: DS402 homing method 14

Procedures:

Case 1:

Axis does not activate the reference switch while moving towards the limit switch:

1. Movement in negative direction with profile data set 1.
2. Reversing to negative travel range limit switch.
3. Reversing with positive edge of the reference switch and change to profile data set 2.
4. Negative edge of the reference switch activates touch probe detection.
5. The following positive edge of the encoder zero pulse/touch probe sensor sets the reference.
6. Absolute positioning to target position (

C02643

) with profile data set 2 (if

C02641

= "0").

Case 2:

Axis first activates the reference switch while moving towards the limit switch:

1. Movement in negative direction with profile data set 1.
2. Positive edge of the reference switch activates profile data set 2.
3. Negative edge of the reference switch activates touch probe detection.
4. The following positive edge of the encoder zero pulse/touch probe sensor sets the reference.
5. Absolute positioning to target position (

C02643

) with profile data set 2 (if

C02641

= "0").

Case 3:

Axis already stands on the reference switch:

1. Movement in negative direction with profile data set 2.
2. Negative edge of the reference switch activates touch probe detection.
3. The following positive edge of the encoder zero pulse/touch probe sensor sets the reference.
4. Absolute positioning to target position (

C02643

) with profile data set 2 (if

C02641

= "0").

 Touch probe/zero pulse

 Reference switch

 Negative travel range limit switch