1 parameter setting, 12 basic drive functions, Stop – Lenze E94AxPExxxx User Manual

Page 447

Advertising
background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

447

12

Basic drive functions

12.5

Manual job, encoderless

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.5.1

Parameter setting

• Parameterising dialog box in»Engineer«: Tab Application parameters  Dialog level Overview

All basic functions Manual jog (OL)

• Short overview of the parameters for manual jog, encoderless:

Parameter

Info

Lenze setting

Value Unit

C02770/1

EnableManualMode

0: Deactivate

C02770/2

JogPositive

0: Deactivate

C02770/3

JogNegative

0: Deactivate

C02770/4

ActivateDataBit1

0: Deactivate

C02770/5

ActivateDataBit2

0: Deactivate

C02771/1...4

Frequency

• Field frequency f

d

with which the current vector

rotates.

1.0 Hz

C02772/1...4

Start angle

0.0 °

C02773/1...4

Current

• R.m.s. value of the current vector which is injected

with the parameterised frequency/starting angle.

• 100 % ≡ I

max_device

(

C00022

)

10.00 %

C02774/1...4

Acceleration time

1.000 s

C02775/1...4

Deceleration time

1.000 s

C02776/1...4

Max. activation time

1.000 s

C02779

Mol_SetpointCurrent

- A

C02780

Mol_dnState

-

C02781

ManualJogOpenLoop: Dig. signals

-

Highlighted in grey = display parameter

Stop!

At the frequency f

d

= 0 Hz, the r.m.s. value increases to 141 % of the current

parameterised in

C02773/x

. As a result, the connected motor can be destroyed!

Remedy: Activation of a derating curve in i2xt monitoring or limitation of the

parameterised current in

C02773/x

to 71 % of the rated motor current.

Motor

monitoring (I

2

xt)

( 263)