15 parameter reference – Lenze E94AxPExxxx User Manual

Page 747

Advertising
background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

747

15

Parameter reference

15.2

Parameter list

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

77 Calculate current controller

parameters

From software version V2.0

Calculates the gain and reset time of the current

controller.

• Usually not required for a Lenze motor.

• The device command is no identification procedure

for determining the current controller parameters!

Calculate current controller parameters

78 Calculate speed controller

parameters

From software version V2.0

Calculates the gain, reset, and rate time of the speed

controller.

• The device command is no identification procedure

for determining the speed controller parameters!

Calculate speed controller parameters

91 CAN on-board: Reset node

Reinitialise "CAN on board" interface.

• Required when changing the baud rate, node address,

or identifiers.

"CAN on board" system bus

92 CAN module: Reset node

Reinitialises CANopen interface of the CANopen

communication module.

• Required when changing the baud rate, node address,

or identifiers.

93 CAN on-board: Pred.Connect.Set

Sets basic identifier for the "CAN on board" interface

according to the "Predefined Connection Set"

(DS301 V4.02).

"CAN on board" system bus

94 CAN module: Pred.Connect.Set

Sets basic identifier for the CANopen interface of the

CANopen communication module according to the

Predefined Connection Set" (DS301 V4.02).

95 CAN on-board: Identify node

Detects nodes connected to the "CAN on board"

interface.

• The result of the CAN bus scan is displayed in

C00393

.

"CAN on board" system bus

96 CAN module: Identify node

Detects the nodes connected to the CANopen interface

of the CANopen communication module.

• The result of the CAN bus scan is displayed in C13393

(for MXI1) or C14393 (for MXI2).

101 Unbind/bind Ethernet module MXI1 Reinitialises the Ethernet interface of the Ethernet

communication module in module slot MXI1.

• Required when a new setting for an IP or gateway

address is to be accepted without mains switching.

102 Unbind/bind Ethernet module MXI2
201 Activate parameter set 1

Loads parameter set 1 from the memory module.

• Only possible when the application has stopped and

the controller is inhibited.

202 Activate parameter set 2

Loads parameter set 2 from the memory module.

• Only possible when the application has stopped and

the controller is inhibited.

203 Activate parameter set 3

Loads parameter set 3 from the memory module.

• Only possible when the application has stopped and

the controller is inhibited.

204 Activate parameter set 4

Loads parameter set 4 from the memory module.

• Only possible when the application has stopped and

the controller is inhibited.

301 Archive parameter set 1

Saves the current parameter set as parameter set 1 in the

memory module.

302 Archive parameter set 2

Saves the current parameter set as parameter set 2 in the

memory module.

Parameter | Name:

C00002 | Device command

Data type: UNSIGNED_32

Index: 24573

d

= 5FFD

h

Advertising