Encoder evaluation

7.3

Parameter setting

294

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.3.7

Parameterisation of a Hiperface® encoder with increased initialisation time

This function extension is available from software version V5.0 onwards!

Application: A Hiperface® encoder is to be used at the controller which has an initialisation time

that differs from the Hiperface specification. This applies to e.g. the absolute value encoders of the

types SEK37, SEL37, SEK52 and SEL52 of the Sick company.
In case of Hiperface® encoders with increased initialisation time, an error message occurs after

switching on the controller

0x007b001a

("absolute value encoder: communication error"). This

error can be acknowledged but occurs again after every switch-on.
In order to avoid the error message, it is possible to consider the increased initialisation time of the

encoder in

C00412

.

For the absolute value encoders of the types SEK37, SEL37, SEK52 and SEL52 of the Sick company,

the required initialisation time in

C00412

is = 1200 ms.

The initialisation time required for each case can be obtained from the respective absolute value

encoder data sheet.