4plc functionality – Lenze E94AxPExxxx User Manual

Page 60

Advertising
background image

4

PLC functionality

4.6

Network communication

60

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

PDO mapping in »PLC Designer«
The access to the ports and therefore to the CAN data is effected via global variables which are

already declared in the Ports list of the global variables.

Standard project "PLC_Application.pro"

In the PLC logic you can access the global "Port“ variables. The name of the variables is identical to

the port.
Each port variable has an individual data type which is defined in the standard project in the Data

types tab.
The CAN mapping of the ports is effected via codes which are defined in the

AutomationSuite_ObjectDirectory list in the parameter manager.

Note!

Without the "AutomationSuite_ObjectDirectory" parameter list the PDO mapping can no

longer be carried out.
If you have deleted the "AutomationSuite_ObjectDirectory" parameter list, the global

variables "Ports", or the associated data types in your project, you can restore the missing

objects by importing them from a standard PLC application.