12

Basic drive functions

12.4

Manual jog

438

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Outputs

Identifier

DIS code | data type

Value/meaning

MAN_dnState

C02638

| DINT

Status (bit coded)

• When the basic function is not enabled, all bits are set to "0".

• Bits which are not listed are not assigned with a status (always "0").

Bit 1 Manual jog is active.
Bit 2 Manual jog is completed.
Bit 3 Acceleration/deceleration phase is active.
Bit 5 CCW rotation is active.

Bit 15 Fault in basic function active (group signal).
Bit 16 Stop by simultaneous selection of negative direction and retraction

of limit switch.

Bit 17 Stop by simultaneous selection of positive and negative direction.
Bit 18 Stop by simultaneous selection of positive direction and retraction of

limit switch.

Bit 19 Speed override ≤1 %
Bit 20 Speed 2 (

C02621

) active.

Bit 21 Speed 1 (

C02620

) active.

Bit 22 Stop by selection of positive direction and simultaneous activation

of the positive software limit position or the positive limit switch.

Bit 23 Stop by selection of negative direction and simultaneous activation

of the negative software limit position or the negative limit switch.

Bit 24 General abort process (ramp down of the speed setpoint)

• Takes place e.g. when a manual direction initiator is released or

due to an impermissible state (see bit 16, 17, 18, 22, 23).

Bit 25 Stopping is active.

• Basic function enabled for the first time but no manual jog has

been requested/is active yet or current speed is higher than the

manual jog speed.

Bit 26 Home position is not known.
Bit 27 No intermediate stop position available.
Bit 30 Profile generation error.

MAN_bEnabled

C02639/6

| BOOL

Status signal "Basic function is enabled"

TRUE Manual jog via the control inputs is possible.

• The MAN_bEnable enable input is set to TRUE and the controller

is in the "Manual jog active" function state.

MAN_bActive

C02639/7

| BOOL

Status signal "Basic function is active"

TRUE Manual jog is active (the drive axis is moving).