8.2.4

Overvoltage in the DC bus

If, due to a too high braking energy, the DC-bus voltage exceeds the overvoltage threshold which

results from the mains voltage setting in

C00173

, the "Overvoltage in the DC bus" error message is

output and the response set in

C00600

is activated (default setting: "Trouble").

Stop!

The brake resistor can be thermally overloaded. Carry out protective measures suitable

for the installation, e.g.:

• Parameterisation of an error response in

C00574

and evaluation of the parameterised

error message within the application or within the machine control.

• External interconnection using the thermal contact on the brake resistor (e.g. supply

interruption via the mains contactor and activation of the mechanical brakes).

Note!

If the system is dimensioned correctly, this monitoring function should not respond. If

individual rated data of the actually connected brake resistor are not known, they have

to be determined "empirically".

Note!

For hoist applications, the "Fault" response should be selected in

C00600

(in combination

with an emergency stop via mechanical brakes).