10 "can on board" system bus – Lenze E94AxPExxxx User Manual

Page 371

Advertising
background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

371

10

"CAN on board" system bus

10.9

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Life guarding event
The "Life Guarding Event" is triggered in the NMT slave if this has not received an RTR telegram from

the NMT master within the "Node Life Time":

• In the Lenze setting, the NMT slave changes from the "Operational" communication status into

the "Pre-Operational" communication status.

C00625

or the

I-1029

object serve to set a status change.

• The NMT master receives an emergency telegram containing emergency error code 0x8130.
• The response parameterised in

C00614

takes place (Lenze setting: "No response").

Node guarding event
The "Node Guarding Event" is triggered in the NMT master if this has not received any response to

its RTR telegram from the requested NMT slave within the "Node Life Time" or the toggle bit in the

response telegram has not changed within the "Node Life Time".

• In the Lenze setting, the NMT master changes from the "Operational" communication status

into the "Pre-Operational" communication status.

C00625

or the

I-1029

object serve to set a status change.

• The response parameterised in

C00612/1...32

takes place (Lenze setting: "No response"). The

response in the NMT master can be set individually for each monitored node.

Note!

The "Life Guarding Event" can only be triggered in the NMT slave if at least one RTR

telegram has been received successfully from the NMT master.

Note!

The "Node Guarding Event" can only be triggered in the NMT master if at least one

response has been received successfully from the requested NMT slave.