File projectselection.dat defect [0x008c0000, 0x00870008, 0x00890000 – Lenze E94AxPExxxx User Manual

Page 702: 0x00880000, 0x008c0000, 14 diagnostics & fault analysis

Advertising
background image

14

Diagnostics & fault analysis

14.7

Error messages of the operating system

702

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CAN on board PDO manager: Faulty configuration [0x00870008]

CAN on board SDO server: Faulty configuration [0x00880000]

CAN on board SDO client: Faulty configuration [0x00890000]

File ProjectSelection.dat defect [0x008c0000]

Module ID (decimal)

Error ID (decimal)

135: "CAN on board": CAN-PDO handler

8

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: CAN-PDO configuration error

• Faulty project download.

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Mapping variables have incorrect CANopen indices

according to DS405.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.

Module ID (decimal)

Error ID (decimal)

136: "CAN on board": CAN-SDO server

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: A configuration error has occurred in the

CAN SDO server.

• Faulty project download.

• Invalid SDO server settings according to DS301V402

in the Engineer or PLC Designer.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.

Module ID (decimal)

Error ID (decimal)

137: "CAN on board": CAN-SDO client

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: A configuration error has occurred in the

CAN SDO client.

• Faulty project download.

• Invalid SDO client settings according to DS301V402 in

the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

Reformat memory module (

C00002

="1030") and repeat

project download.