6motor interface – Lenze E94AxPExxxx User Manual
Page 253
Advertising
![background image](/manuals/566084/253/background.png)
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
253
6
Motor interface
6.8
Parameterisable additional functions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9. Switch on the correction (
= "ON").
• When the correction of the stator leakage inductance is switched on, the same current
characteristic should occur, irrespective of the current magnitude.
• Since the current controller gain is corrected actively, the step responses may differ slightly
compared to the previous measurements. In this case
and
one last time.
10. Save parameter set (
= "11: Save start parameters").