Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

601

12

Basic drive functions

12.13

Cam data management

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.13.6

Behaviour after mains switching

After mains switching, the cam data are loaded from the memory module into the controller

between loading and start of the application.

Note!

During the initialisation no check of the user password takes place, but a check of the

serial number of the memory module is carried out, if this access protection has been

activated by the user in »Cam Designer«. If the serial number specified and the serial

number of the memory module do not match, the cam data are not loaded.

• The "Cam data: serial number" error message is entered in the logbook.
• The "Warning locked" error response occurs.

If a download of cam data that was carried out before mains switching was not

completed correctly, the previous cam data – if available – are loaded by the memory

module.

• The "Cam data restored" error message is entered into the logbook.
• The "Fault" error response occurs.
• After the error is reset (acknowledged), operation with the previous cam data is

possible.