3 led status displays for the system bus, 10 "can on board" system bus – Lenze E94AxPExxxx User Manual

Page 338

Advertising
background image

10

"CAN on board" system bus

10.3

LED status displays for the system bus

338

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.3

LED status displays for the system bus

Both upper LEDs LEDs "CAN-RUN" and "CAN-ERR" on the front of the controller inform about the

CANopen state and report CANopen errors.

[10-2] LED status displays CAN-RUN and CAN-ERR

The meaning can be seen from the table below:

CAN-RUN

CAN-ERR

LED status display

Meaning

CAN-RUN

CAN-ERR

CANopen state

CANopen error

Only CAN-ERR is on

-

Bus off

CAN-RUN and CAN-ERR jitter

Automatic detection of the baud rate is active.

CAN-RUN is blinking every 0.2 seconds | CAN-ERR is off

Pre-Operational

-

CAN-RUN is blinking every 0.2 seconds | CAN-ERR 1 x blinking, 1

s off

Warning Limit reached

CAN-RUN is blinking every 0.2 seconds | CAN-ERR 2 x blinking, 1

s off

Node Guard Event

Only CAN-RUN is on

Operational

-

CAN-RUN on | CAN-ERR 1 x blinking, 1 s off

Warning Limit reached

CAN-RUN on | CAN-ERR 2 x blinking, 1 s off

Node Guard Event

CAN-RUN on | CAN-ERR 3 x blinking, 1 s off

Sync Message Error

CAN-RUN is blinking every 1 second | CAN-ERR is off

Stopped

-

CAN-RUN is blinking every 1 second | CAN-ERR 1 x blinking, 1 s off

Warning Limit reached

CAN-RUN is blinking every 1 second | CAN-ERR 2 x blinking, 1 s off

Node Guard Event