4 "ls_analoginput" system block, Ls_analoginput" system block, Analog inputs – Lenze E94AxPExxxx User Manual
Page 318: 9i/o terminals
![background image](/manuals/566084/318/background.png)
9
I/O terminals
9.2
Analog inputs
318
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.4
"LS_AnalogInput" system block
Output
Data type
Value/meaning
AIN1_dnIn_n
DINT
Analog input 1
• Scaling:
±2
30
≡ ±10 V for use as a voltage input
±2
30
≡ ±20 mA for use as a current input
AIN2_dnIn_n
DINT
Analog input 2
• Scaling: ±2
30
≡ ±10 V
AIN1_bCurrentError
BOOL
Status signal "Current input error"
• Only when analog input 1 is used as current input.
• Application: Cable-breakage monitoring of the 4 ...20 mA circuit.
TRUE |I
AIN1
| < 2 mA
A1+
A1-
A1-
A1R
A2+
A2-
AIN1_dnIn_n
AIN1_bCurrentError
AIN2_dnIn_n
X3
LS_AnalogInput
250
C02731/1 C02730/1 C02732/1
C02731/2 C02730/2 C02732/2
C02800/1
C02800/2