I/O terminals

9.2

Analog inputs

316

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2

Analog inputs

The controller has two analog inputs that can be used to detect differential voltage signals in the

range of ±10 V, e.g. analog speed setpoint selections or the voltage signals of an external sensor

(temperature, pressure, etc.).

• Optionally, analog input 1 can also be used to detect current setpoints.

9.2.1

Terminal assignment/electrical data

Terminal

Application

Electrical data

X3/A1-

X3/A1+

Differential voltage input 1

(no jumper between A1R and A1-

Level: -10 V ... +10 V

Resolution: 11 bits + sign

Scaling: When

C00034

= "0":

±10 V ≡ ±2

30

Conversion rate: 1 kHz

Current input

(jumper between A1R and A1-)

Level: -20 mA ... +20 mA

Resolution: 10 bits + sign

Scaling: When

C00034

= "1":

-20 mA ... -4 mA = -2

30

... 0

+4 mA ... +20 mA = 0 ... 2

30

When

C00034

= "2":

±20 mA ≡ ±2

30

Conversion rate: 1 kHz

X3/A2-

X3/A2+

Differential voltage input 2

Level: -10 V ... +10 V

Resolution: 11 bits + sign

Scaling: ±10 V ≡ ±2

30

Conversion rate: 1 kHz