C00990 | flying restart: activation, C00991 | flying restart: current, C00992 | flying restart: start frequency – Lenze E94AxPExxxx User Manual

Page 853: C00993 | flying restart: integration time, C00994 | flying restart: min. deviation, C00990, D in, C00991, C00992, C00993

Advertising
background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

853

15

Parameter reference

15.2

Parameter list | C00990

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00990

C00991

C00992

C00993

C00994

Parameter | Name:

C00990 | Flying restart: Activation

Data type: UNSIGNED_32

Index: 23585

d

= 5C21

h

Note!

Only deactivate the flying restart for the V/f control or sensorless vector control if it is ensured that the drive is

always at standstill in the case of controller enable!

Flying restart fct.

Selection list

(Lenze setting printed in bold)

0 Off
1 On

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00991 | Flying restart: Current

Data type: INTEGER_32

Index: 23584

d

= 5C20

h

Flying restart fct.

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

100 15 %

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00992 | Flying restart: Start frequency

Data type: INTEGER_32

Index: 23583

d

= 5C1F

h

Flying restart function

Setting range

(min. value | unit | max. value)

Lenze setting

-600.0

Hz

600.0 20.0 Hz

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00993 | Flying restart: Integration time

Data type: UNSIGNED_32

Index: 23582

d

= 5C1E

h

Flying restart function

Setting range

(min. value | unit | max. value)

Lenze setting

1

ms

6000 60 ms

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00994 | Flying restart: Min. deviation

Data type: UNSIGNED_32

Index: 23581

d

= 5C1D

h

Flying restart function

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

°

90.00 5.00 °

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100